Triad control transformers come with tamper resistant shrouds for safety and a steel bracket welded to the bottom of the transformer for ease of mounting. These transformers are design and have the safety agency recognition for application where a Class 2 transformer is necessary. Some of the applications would include, but not limited to HVAC, Control boards, Lighting, etc.
Unit of Measure
Specifications
Primary Input Voltage |
N/A 120 V |
Secondary Output Voltage |
N/A 24 V |
Maximum Power |
N/A 40 V·A |
Connections |
N/A Input: Quick Disconnect tabs, 0.5 x 0.25 x 0.032 Output: Quick Disconnect tabs, 0.5 x 0.187 x 0.032 |
Typical Voltage Regulation from Full Load to No Load |
N/A 15 % |
Typical Temperature Rise |
N/A <40 ºC |
Hipot |
N/A 1500 VAC - Input to Output, Input and Output to Core |
Inherently Limited |
N/A No Fusing Required. |
Input Frequency |
N/A 50 Hz60 Hz |
Weight |
N/A 1.50 lb |
Construction |
N/A Three flange bobbin construction with primaries and secondaries wound side by side for low capacitive coupling. |
Agency File |
N/A
UL: File E65390, UL 5085-3 (1585), Class 2 Transformer cUL: File E65390, UL 5085-3 (1585) For Canadian Use (CSA 22.2, No.66.3-06) |
RoHS Compliance |
N/A As of manufacturing date February 2016, all standard products meet the requirements of 2015/863/EU, known as the RoHS 3 initiative. |